Performance Analysis of Controlled Reclosing Procedure of Transmission Lines under Non-ideal Conditions

Tamanho: px
Começar a partir da página:

Download "Performance Analysis of Controlled Reclosing Procedure of Transmission Lines under Non-ideal Conditions"

Transcrição

1 64 IEEE LATIN AMERICA TRANSACTIONS, VOL. 6, NO. 4, APRIL 208 Performance Analysis of Controlled Reclosing Procedure of Transmission Lines under Nonideal Conditions R. C. F. Gregory, A. C. Santos, J. C. Oliveira, M. L. R. Chaves, K. M. C. Dantas, Member, IEEE, W. L. A. Neves, Member, IEEE, D. Fernandes Jr., Member, IEEE and L. C. A. Fonseca Abstract Transient overvoltage phenomenon related to transmission lines switching procedures is a quite well known subject, as well as the corresponding site effects that may affect the electrical system reliability as a whole. In the face of these occurrences, if mitigating measures are not taken, insulation faults in transmission lines and other components of the system can occur with relative frequency. Added to a set of classic procedures for the minimization of these phenomena, other possibilities, unconventional, have presented themselves as attractive options to the process in question. In this context, this paper explores the potentialities of a strategy established in the literature, which relies on socalled controlled switching technology. This procedure consists in the determination and use of optimum instants for the operational reestablishment of the line operation, after a possible disconnection and, from these, the switches are made without the undesirable overvoltages mentioned herein. Despite the fact that the fundamentals of this methodology are known, this investigation is imbued with the purpose of including nonideal operational conditions that can, for real situations in the field, impact on the effectiveness of the method performance. Keywords ATP, controlled switching, overvoltages, transients, transmission lines. switching I. INTRODUÇÃO A S SOBRETENSÕES transitórias, no que tange às manobras de energizações e religamentos das linhas de transmissão, podem provocar incomensuráveis efeitos danosos à operação do sistema elétrico, uma vez que são capazes de comprometer o isolamento dos equipamentos presentes nestes complexos quando da manifestação de picos de tensão mais proeminentes àqueles definidos em projeto []. De fato, reconhecese que os surtos de manobras podem manifestar R. C. F. Gregory, Universidade Federal de Uberlândia, Uberlândia, Brasil, raquel.filiagi@gmail.com A. C. Santos, Instituto Federal de Educação, Ciência e Tecnologia do Triângulo Mineiro, Uberaba, Brasil, andreiacrico@iftm.edu.br J. C. Oliveira, Universidade Federal de Uberlândia, Uberlândia, Brasil, jcoliveira@ufu.br M. L. R Chaves, Universidade Federal de Uberlândia, Uberlândia, Brasil, lynce@ufu.br K. M. C. Dantas, Universidade Federal de Campina Grande, Campina Grande, Brasil, karcius@dee.ufcg.edu.br W. L. A. Neves, Universidade Federal de Campina Grande, Campina Grande, Brasil, waneves@dee.ufcg.edu.br D. Fernandes Jr., Universidade Federal de Campina Grande, Campina Grande, Brasil, damasio@dee.ufcg.edu.br L. C. A. Fonseca, Companhia Hidro Elétrica do São Francisco, Recife, Brasil, lfonseca@chesf.gov.br Corresponding author: R. C. F. Gregory sobretensões excepcionalmente elevadas [2], as quais são capazes de atingir valores próximos a 5,0 p.u. [3], o que torna imprescindível a adoção de procedimentos capazes de amainar tais eventos. No contexto da tecnologia aplicável à mitigação da problemática em foco, ressaltase, inicialmente, o emprego dos tradicionais disjuntores com resistores de préinserção (RPI). Deveras, em se tratando da eficiência do método, o mesmo é capaz de atenuar as sobretensões aos níveis admissíveis, quando da escolha e instante de inserção apropriados do resistor [4]. Todavia, tais dispositivos podem apresentar um número substancialmente elevado de falhas operacionais, acarretando no aumento dos custos gerais de manutenção e reposição de componentes [5], [6]. Dessarte, é cógnito que os problemas pertinentes às sobretensões de manobras em linhas de transmissão podem ser efetivamente abrandados mediante a aplicação das mais diversas técnicas de chaveamento controlado [7], [8], cuja terminologia intitula os dispositivos capazes de identificar regiões ou instantes propícios para o chaveamento dos contatos dos disjuntores [9], [0]. Esta estratégia, por sua vez, elimina a necessidade do RPI, mostrandose técnica e economicamente atrativa para o aumento da confiabilidade do sistema [], []. Muito embora existam inúmeras referências na literatura correlatas ao desempenho das estratégias baseadas em chaveamentos controlados [2], [6], [2], ressaltase que tais trabalhos contemplam condições ideais de operação do sistema elétrico, isto é, quando não há presença de tensões com perfis prédesequilibrados, ou quaisquer outras anomalias que depreciam a qualidade da energia elétrica em sistemas reais. Adicionalmente, devese reconhecer que, na ocorrência de curtoscircuitos, o valor da impedância de falta pode afetar o comportamento das frequências oscilatórias remanescentes na linha de transmissão [3] as quais se fazem presentes durante as manobras de religamentos, salientando a necessidade de estudos pertinentes à temática ora mencionada. Diante dessa conjuntura, o presente trabalho encontrase alicerçado na apresentação de uma síntese dos conceitos físicos e matemáticos de uma estratégia destinada a cumprir as metas ora postas. Uma vez definidos os fundamentos que norteiam a metodologia em pauta, a qual se baseia em [2], esta é implementada computacionalmente no Alternative Transients Program (ATP), utilizando um complexo elétrico típico pertencente à rede básica do Sistema Interligado Nacional (SIN). A partir desta base para estudos, são conduzidas investigações quando da ocorrência de curtos

2 FILIAGI GREGORY et al.: PERFORMANCE ANALYSIS 65 circuitos assimétricos ao longo da linha de transmissão, considerando fatores de influência atrelados ao valor da impedância de falta e eventuais desequilíbrios presentes nas tensões, ambicionando, assim, avaliar a eficácia da metodologia frente às adversidades operativas frequentemente encontradas em campo. II. FUNDAMENTOS DA METODOLOGIA DO CHAVEAMENTO CONTROLADO Os problemas alusivos às sobretensões devido às mudanças repentinas de estado dos disjuntores em linhas de transmissão podem ser efetivamente amainados mediante a aplicação das mais diversas estratégias de chaveamentos controlados. De fato, existe uma vasta literatura atrelada ao referido tema, com destaque às manobras de energizações e religamentos de linhas em sistemas de transmissão [6], [3]. É cógnito que as energizações são manobras programadas frequentemente realizadas no sistema elétrico, as quais são tipicamente de natureza trifásica. Todavia, devido à dispersão mecânica e ao arco elétrico serem intrínsecos ao processo de manobra das chaves, os polos do disjuntor não são fechados simultaneamente [4], acarretando em sobretensões transitórias capazes de atingir o dobro do seu valor nominal [5]. Por outro lado, as manobras de religamento são realizadas posteriormente à interrupção súbita no fornecimento da energia provinda da linha de transmissão. Por conseguinte, após a abertura da linha, permanecerá uma tensão residual a qual se fará presente durante o processo do religamento, provocando sobretensões substancialmente elevadas, sobretudo, quando as tensões da fonte apresentam polaridade inversa à da linha [2]. Quando a linha de transmissão é dotada de compensação reativa em derivação, a referida tensão residual apresenta composição física similar a um oscilador, visto que esta se comporta como uma fonte de excitação para o circuito envolvendo as capacitâncias da linha e a indutância dos reatores de compensação. Assim sendo, há de se reconhecer um comportamento oscilatório contendo diferentes componentes de frequência, as quais são dependentes do arranjo de transposição da linha, do seu grau de compensação e do tipo de defeito que originou sua abertura [3]. Deveras, quando não há a manifestação de defeitos ao longo condutor, é possível inferir que o conjunto formado pela linha e reator contém duas frequências naturais de oscilação, enunciadas por () e (2), as quais podem ser determinadas desprezandose a reatância da linha uma vez que há predominância do reator de compensação [6]. = = 2! 2! (!") (!") () (2), (! = 0,) parâmetros elétricos do conjunto linhareator no domínio modal. Isto posto, reconhecese que, quando há presença de curtoscircuitos, as frequências oscilatórias podem apresentar comportamento particular para cada tipo de falta, o que possibilita, em alguns casos, o estabelecimento de meios capazes de identificar o instante de sua extinção. Diante do exposto, serão enunciadas, na sequência, as peculiaridades dos diferentes tipos de curtoscircuitos existentes no sistema elétrico, cujas respectivas frequências de oscilação serão obtidas por transformações modais empregandose a matriz de Karrenbauer [5]. A. Faltas faseterra Na ocorrência de um curtocircuito faseterra, assumindo um arranjo de transposição ideal e desprezandose a impedância de falta, os circuitos modais podem ser acoplados tal como ilustrado na Fig.. L v C L2 v2 C2 L0 v0 C0 i Figura. Arranjo no domínio modal representativo de uma falta faseterra. Do exposto, temse que, durante a falta, a soma das tensões modais resulta em (3). (3) = 0 (! = 0,, 2) tensões no domínio modal. Sabendo que os parâmetros do conjunto linhareator, referentes aos modos e 2, são idênticos, é possível obter as expressões das frequências oscilatórias alusivas ao modo e modo 0, as quais são enunciadas por (2) e (4), respectivamente. = 2 2! ( 2 ) (!") (4) Imediatamente após o término da falta, o comportamento descrito por (3) deixa de ser observado, uma vez que os circuitos modais se desagregam e as frequências de oscilação passam a ser definidas, novamente, por () e (2). Deveras, analisando as expressões supracitadas, é possível inferir que o comportamento das tensões residuais durante a falta e após seu término é dissemelhante, o que possibilita identificar a extinção de curtoscircuitos dessa natureza. B. Faltas fasefase Para faltas do tipo fasefase, o arranjo dos circuitos modais é tal qual a configuração apresentada na Fig. 2.

3 66 L0 IEEE LATIN AMERICA TRANSACTIONS, VOL. 6, NO. 4, APRIL 208 v0 C0 L v C L2 v2 C2 Figura 2. Arranjo no domínio modal representativo de uma falta fasefase. Dessa forma, segue que a expressão das tensões modais pode ser enunciada em conformidade com (5). Durante a falta, o comportamento da frequência de oscilação referente ao modo resultará na expressão (2). De fato, é possível que o modo 0 seja excitando durante a abertura da linha, acarretando no surgimento de outra frequência de oscilação definida por (). Por consequência, concluise que não há alteração no comportamento dos osciladores após a extinção do curtocircuito, uma vez que suas frequências permanecem definidas pelas expressões () e (2). Sendo assim, há uma carência de elementos capazes de detectar o término de faltas desse gênero a partir da análise do comportamento da tensão residual [3]. C. Faltas fasefaseterra Quando ocorrem curtoscircuitos envolvendo duas fases da linha de transmissão e a terra, os circuitos modais são conectados similarmente ao arranjo apresentado na Fig. 3, considerando as mesmas premissas adotadas no tópico precedente. L v C L2 v2 C2 L0 v0 C0 Figura 3. Arranjo no domínio modal representativo de uma falta fasefaseterra. Assim procedendo, temse a expressão que rege o comportamento das tensões residuais durante a submissão de faltas fasefaseterra, em consonância com (6). (6) = = Portanto, durante o curto, há na fase sã apenas uma frequência de oscilação definida por (7).!= D. Faltas trifásicas O arranjo representativo de um curtocircuito trifásico encontrase exposto na Fig. 4. (5) = =! fasefaseterra será tratada de forma análoga aos defeitos faseterra, isto é, considerando cada fase individualmente. Sendo assim, na manifestação de ambos os tipos de faltas, o critério para a detecção do seu término encontrase exposto em (3). 2 2! ( 2 ) (!") (7) Uma vez extinta a falta, a igualdade obtida em (6) deixa de ser válida e as frequências de oscilação apresentam valores determinados por () e (2), evidenciando a distinção do comportamento dos osciladores nos períodos supra referidos. Ambicionando padronizar a estratégia de controle que será explorada na seção subsequente, a análise da extinção de faltas L0 v0 C0 L v C L2 v2 C2 Figura 4. Arranjo no domínio modal representativo de uma falta trifásica não aterrada. No ponto da falta, temse que as tensões modais são definidas de acordo com (8). = = 0 (8) Na submissão de defeitos trifásicos, quando não há o envolvimento da terra, as tensões modais e 2 são nulas. Ainda que o circuito modal 0 possa ser excitado no momento de abertura da linha, esta componente é rapidamente amortecida. Por outro lado, quando a terra faz parte do defeito, os circuitos modais 0, e 2 são curtocircuitados, sendo praticamente inexistente a presença da tensão residual na linha de transmissão, uma vez que não há energia armazenada nas suas capacitâncias. Deveras, percebemse as dificuldades na definição de meios capazes de identificar o término de curtoscircuitos dessa natureza. Diante dessa constatação, segue que a estratégia adotada para o chaveamento controlado restringese aos religamentos precedidos por defeitos faseterra e fasefaseterra [3]. É fato que os fundamentos supramencionados encontramse alicerçados em premissas que, via de regra, não são encontradas em situações reais, visto que as impedâncias de falta apresentam valores não nulos. Não obstante este reconhecimento, vale aqui ressaltar que as implicações das referidas alegações não depreciarão os resultados dos estudos, uma vez que, na sequência, serão definidas estratégias para sanar eventuais fragilidades que, por ventura, poderiam se manifestar. III. ESTRATÉGIA PARA O CHAVEAMENTO CONTROLADO E IMPLEMENTAÇÃO NO SIMULADOR ATP Uma vez definidas as peculiaridades dos fenômenos ora postos, a metodologia do religamento rápido e controlado foi implementada no simulador ATP, o qual se apresenta como ferramenta robusta e de renomada aplicação para análise de transitórios em sistemas elétricos [7]. Ressaltase que a referida estratégia, a qual foi embasada na metodologia desenvolvida em [3], consistiu na elaboração de duas MODELS denominadas por M (vermelho) e M2 (azul), em

4 FILIAGI GREGORY et al.: PERFORMANCE ANALYSIS 67 conformidade com o diagrama de blocos apresentado na Fig. 5. SISTEMA ELÉTRICO DE POTÊNCIA (SEP) Trip para o religamento da linha Amostragem dos sinais Análise do acoplamento eletromagnético Extrapolação dos sinais e estimativa dos instantes ótimos N Há defeito na linha? S FT ou FFT? N S Tempo de duração da falta t > tmorto? S N N t > tmorto? Religamento bloqueado S Religamento automático pelo SEP Figura 5. Diagrama esquemático da lógica de controle implementada em M (vermelho) e M2 (azul). Em ambas as MODELS, considerouse um passo de integração de /960, resultando em uma taxa de 6 amostras por ciclo. Apenas os sinais das tensões trifásicas provenientes da linha foram solicitados como entradas de M. É importante salientar que os aspectos atrelados ao reconhecimento do tipo de falta e das fases envolvidas perfazem os dados solicitados pelas MODELS. Identificada a existência de um curtocircuito na linha de transmissão, os disjuntores terminais sofrem abertura imediata. De fato, para que a linha possa ser reinserida no sistema é necessário, primeiramente, identificar se a falta foi extinta dentro de um tempo morto. Caso o curtocircuito persista, devese interromper o processo do religamento, visando garantir que a manobra não ocorra sob defeito. Tendo em vista o atendimento a este quesito, a estratégia adotada baseouse na observação dos sinais das tensões modais, empregandose a expressão (9) [2]. ( ) = (9) A partir desta correlação presumese que: Se ( ) =, a falta ainda persiste; Se ( ), a falta foi extinta. Entretanto, em se tratando de uma situação real, a igualdade expressa em (9) deixa de ser rigorosamente observada, já que a soma das tensões modais é proporcional a impedância do defeito [8]. Nestas circunstâncias, a alternativa fundamentase na comparação da proximidade entre os valores de ( ) e por meio do emprego do coeficiente de determinação R² [9], o qual foi implementado na MODELS M, em consonância com (0). = " " (0)! soma quadrática das diferenças entre os sinais e ( ), tomadas ponto a ponto, em um intervalo de N amostras;! soma quadrática das diferenças entre as amostras de e o valor médio desse sinal, no intervalo de N amostras. Após a abertura dos disjuntores, esperase que o coeficiente R² se apresente com valores próximos a um e que a referida grandeza seja nula após o término da falta. Identificada a extinção da falta, iniciase a estimativa do comportamento dos sinais em instantes futuros, cujo algoritmo foi implementado na MODELS M2. As entradas que perfazem a MODELS são dependentes da tensão em uma das fases da barra que compõe o terminal emissor, das tensões trifásicas disponibilizadas pela linha de transmissão e do sinal de saída da MODELS M. De fato, M2 só será iniciada no instante em que M enviar um sinal indicando que o curtocircuito findouse. Imediatamente após o término da falta, as amostras das tensões do lado da fonte e da linha são convertidas para o domínio modal. Posteriormente, iniciase o algoritmo de detecção de passagens por zero por meio do produto de duas amostras consecutivas da tensão modal, definidas por! e! (Fig. 6), cujo resultado deve ser negativo na ocorrência de uma passagem por zero [20]. v' 0 t' t" t0 t v" Figura 6. Detecção de passagem por zero da tensão modal. A partir da Fig. 6, definese o momento no qual a tensão no domínio modal atinge um valor equivalente a zero, tal como enunciado em (). =!!!!!! ()! e! amostras consecutivas da tensão no domínio modal, consideradas imediatamente próximas ao instante de passagem por zero.! e! instantes nos quais duas amostras consecutivas da tensão modal encontramse mais próximas de. A etapa seguinte consiste na obtenção das amplitudes e frequências das tensões presentes em ambos os lados do disjuntor. Dessarte, estimase o comportamento dos sinais mediante a extrapolação das componentes de frequência da tensão em cada fase, tanto do lado da fonte quanto do lado da

5 68 IEEE LATIN AMERICA TRANSACTIONS, VOL. 6, NO. 4, APRIL 208 linha. Objetivando maior precisão ao processo, este após três passagens por zero " contadas a extinção da falta. A Fig. 7 ilustra o exposto denominado modo genérico, considerando que o eliminado no momento identificado por! [20]. T T2 T(n) V2 é iniciado partir da para um defeito é T(n) Por fim, o diagrama da Fig. 8 ilustra a configuração final implementada. Após a detecção do curtocircuito, entendese que os disjuntores da linha (DJ e DJ2) encontramse na condição aberta, os quais são controlados pela MODELS M2. No diagrama, R e R2 representam os reatores de compensação da linha em questão. M2 Terminal Emissor V(n) DJ t V LT R DJ2 R2 Figura 8. Diagrama esquemático da linha de transmissão submetida ao chaveamento controlado. V(n) t00 t0 t02 t03 t0(n) t0(n) t0(n2) Figura 7. Estimativa da amplitude e período dos sinais de tensão no domínio modal. Do exposto, definemse as expressões da tensão e frequência no domínio modal, em consonância com (2) e (3), respectivamente, cujos valores são renovados quando há novos cruzamentos pelo eixo do tempo. IV. AVALIAÇÃO DO DESEMPENHO DA METODOLOGIA A Fig. 9 exibe o diagrama unifilar do complexo elétrico modelado no simulador ATP. Quixadá Fortaleza II FTZQUI "#! =!! sen 2!"#! "#$%çã! "# = 2!(!) 2!(!) 2 Terminal Receptor M Milagres QUIMLG S. J. Piauí MLGSJP Boa Esperança SJPBSP (2) (3)!! máximo valor absoluto da tensão entre duas passagens por zero; "# frequência modal (mod = 0, ); "#$%çã! tempo de operação típico do disjuntor;!(!) período entre dois instantes de passagem por zero. Definidas as tensões modais, os sinais são agrupados visando compor apenas duas amostras para cada fase, uma a montante e outra a jusante do disjuntor. Isto posto, os sinais são extrapolados durante um intervalo máximo de 00 ms, cujo processo é interrompido quando forem encontrados três instantes apropriados para o fechamento de cada polo. Com o propósito de reconhecer os intervalos favoráveis para o religamento da linha de transmissão, são identificados, primeiramente, os momentos nos quais a tensão entre os contatos do disjuntor é nula. De posse dos instantes supra referidos, efetuase o produto das derivadas destes sinais afim de determinar os intervalos em que ambos possuem a mesma inclinação, cujo período descreve sua menor pulsação [3]. Definidos três momentos apropriados para o chaveamento dos contatos dos disjuntores, classificase apenas um instante para cada polo mediante a análise do acoplamento eletromagnético entre as fases. Neste contexto, observase o menor intervalo de fechamento entre o primeiro e o último polo, ambicionando reduzir eventuais desvios no comportamento da tensão no momento do chaveamento. Sendo assim, três sinais são enviados para os disjuntores conectados aos terminais da linha de transmissão, cujo tempo de manobra é distinto para cada fase e dependente das etapas supracitadas. Figura 9. Diagrama unifilar da configuração implementada no ATP. A estratégia de controle foi aplicada para o chaveamento da linha de transmissão de 500 kv que interliga Milagres à São João do Piauí, considerando Milagres como terminal emissor. As fontes de tensão foram ajustadas para fornecer 550 kv na barra de Milagres. Os parâmetros do sistema encontramse subsequentemente listados em conformidade com [3]. TABELA I PARÂMETROS ELÉTRICOS DAS LINHAS DE TRANSMISSÃO Linha (LT) FTZQUI QUIMLG MLGSJP SJPBSP (Ω/km) 0,026 0,223 0,026 0,242 0,09 0,493 0,025 0,376 (Ω/km) 0,282 0,900 0,282 0,872 0,267,339 0,322,4 (µ /km) 5,877 3,40 5,88 3,448 6,24 2,890 5,20 3,064 Comp. (km) 37,8 268,7 400,0 233,8 TABELA II PARÂMETROS ELÉTRICOS DOS REATORES DE LINHA NA BASE DE 500 KV Linha de Transmissão FTZQUI QUIMLG QUIMLG MLGSJP MLGSJP SJPBSP SJPBSP Subestação Fortaleza II Quixadá Milagres Milagres S. J. Piauí S. J. Piauí Boa Esperança Potência (MVAr) /,70,73 TABELA III PARÂMETROS ELÉTRICOS DOS REATORES DE BARRA Subestação Fortaleza II Quixadá B. Esperança "#$ (kv) Potência (MVAr) /,0,0,0

6 FILIAGI GREGORY et al.: PERFORMANCE ANALYSIS 69 TABELA IV REATÂNCIA PERCENTUAL DO CAPACITOR SÉRIE Linha de Transmissão SJPBSP Subestação S. J. Piauí Reatância (%) 2, TABELA V IMPEDÂNCIA EQUIVALENTE DE THÉVENIN Sequência Positiva (Ω) (Ω) 3,90 06,6 0,4 273,33 Subestação Fortaleza II Boa Esperança Sequência Zero (Ω) (Ω),98 24,49 7,79 00,94 De posse dos parâmetros supramencionados, realizouse a modelagem do sistema elétrico no ambiente ATPDraw, no qual foram simuladas 864 faltas faseterra e fasefaseterra admitindo diferentes anomalias operativas, as quais contemplaram as seguintes condições: Impedâncias de falta de Ω, 0 Ω, 00 Ω e 200 Ω, respectivamente, as quais foram arbitradas em consonância com [2]; Desequilíbrios de tensão de 0%, %, 2% e 3%, cujos valores encontramse próximos aos limites impostos pelas regulamentações vigentes [22]. A. Religamento Após a Ação de Faltas Faseterra Para o estudo em pauta, considerouse a manifestação de 432 curtoscircuitos faseterra envolvendo as fases A, B e C, objetivando analisar possíveis falhas na determinação do tempo de duração da falta e identificar picos de tensão não desejados após atuação do controle. Na sequência, a Tabela VI expõe o desempenho do algoritmo de controle em função dos valores das impedâncias de falta, enquanto a Tabela VII apresenta a eficácia do processo considerando diferentes percentuais de desequilíbrios de tensão provenientes da rede. TABELA VI DESEMPENHO DA ESTRATÉGIA DE CONTROLE EM FUNÇÃO DO VALOR DA IMPEDÂNCIA DE FALTA FALTAS FASETERRA (Ω) Máxima (p.u.),55,55,53,52 Média (p.u.),38,37,35,35 Desvio Padrão 0,06 0,024 0,099 0,0969 Eficácia do Processo 00 % 00 % 00 % 00 % TABELA VII DESEMPENHO DA ESTRATÉGIA DE CONTROLE EM FUNÇÃO DO PERCENTUAL DE DESEQUILÍBRIO FALTAS FASETERRA Desequilíbrio de Tensão Máxima (p.u.) Média (p.u.) Desvio Padrão 0% % 2% 3%,54,53,54,55,36,37,37,37 0,0962 0,0958 0,0998 0,046 Eficácia do Processo 00 % 00 % 00 % 00 % Isto posto, há de se reconhecer que os resultados auferidos ratificam a eficácia da metodologia para o chaveamento de linhas após a ação de curtoscircuitos faseterra. Em se tratando das sobretensões oriundas do religamento, é notável que tais fenômenos foram mantidos a níveis razoáveis, sobretudo, após a manifestação de faltas de maior impedância. Vale salientar que as anomalias operativas impostas aos estudos, atreladas aos desequilíbrios de tensão, foram incapazes de depreciar a eficácia do processo, não impactando, efetivamente, na reinserção da linha de transmissão de forma satisfatória. Não obstante as resultâncias supramencionadas, ressaltase que a aplicação da metodologia ora posta possibilita o aumento da confiabilidade do sistema, visto que o religamento controlado pode ser efetuado em um tempo morto consideravelmente sucinto, fato este que difere de uma manobra de religamento automático, cujo tempo de reinserção é tipicamente superior a 500 ms. B. Religamento Após a Ação de Faltas Fasefaseterra Ambicionando a validação da metodologia do chaveamento controlado no que tange aos curtoscircuitos fasefaseterra, foram desenvolvidas 432 simulações de faltas envolvendo as fases AB, BC e AC do complexo de transmissão ilustrado na Fig. 9. Similarmente ao procedimento adotado para o estudo precedente, foram avaliados os impactos do valor da impedância de falta e desequilíbrios de tensão no processo do chaveamento controlado, visando estimar os percentuais de religamentos bemsucedidos na presença de tais distúrbios. A Tabela VIII exibe a performance do controle para cada valor da impedância de falta. De forma similar, a Tabela IX apresenta a eficácia do processo considerando os diferentes percentuais de desequilíbrio impostos ao sistema sob estudo. Vale enfatizar que os cálculos dos indicadores da eficácia do método encontramse amparados na relação entre a quantidade de religamentos que atingiram sucesso e o número total de tentativas, cujos processos não falhos contemplaram a manifestação de sobretensões abaixo dos níveis impostos por surtos atmosféricos [23] e a correta identificação do intervalo de duração do curtocircuito. TABELA VIII DESEMPENHO DA ESTRATÉGIA DE CONTROLE EM FUNÇÃO DO VALOR DA IMPEDÂNCIA DE FALTA FALTAS FASEFASETERRA (Ω) Máxima (p.u.),66,74,75,64 Média (p.u.),5,58,59,58 Desvio Padrão 0,0635 0,0665 0,0755 0,0320 Eficácia do Processo 00 % 92,59 % 95,37 % 00 % TABELA IX DESEMPENHO DA ESTRATÉGIA DE CONTROLE EM FUNÇÃO DO PERCENTUAL DE DESEQUILÍBRIO FALTAS FASEFASETERRA Desequilíbrio de Tensão Máxima (p.u.) Média (p.u.) Desvio Padrão 0% % 2% 3%,74,74,75,75,56,56,56,57 0,0665 0,0670 0,0738 0,0743 Eficácia do Processo 98,5 % 96,30 % 96,30 % 00 %

7 70 IEEE LATIN AMERICA TRANSACTIONS, VOL. 6, NO. 4, APRIL 208 De posse dos resultados supra postos, constatase que o algoritmo de controle também apresenta desempenho satisfatório para o chaveamento de linhas submetidas a faltas fasefaseterra. De fato, as sobretensões máximas foram mantidas a,75 pu, cujo valor encontrase abaixo dos limites impostos pelos limites impostos aos surtos de manobras em sistemas de 500 kv [23], mesmo na presença de tensões desequilibradas provindas da rede elétrica. Não obstante os indicativos associados com a boa eficácia do processo, no que tange aos religamentos sucedidos de faltas fasefaseterra, ressaltase que sua redução pode estar vinculada com o refinamento do algoritmo de controle, tema este merecedor de maiores investigações para maximização dos percentuais supra obtidos. V. OBSERVAÇÕES FINAIS O presente trabalho visou à apresentação e avaliação de desempenho de uma estratégia baseada em chaveamentos controlados, almejando mitigar as sobretensões provenientes das manobras de disjuntores nas linhas de transmissão. Para tanto, contemplouse, num primeiro momento, a apresentação de uma síntese dos fundamentos físicos e matemáticos da proposta em consonância com desenvolvimentos prévios, os quais foram previamente identificados neste trabalho. A partir do procedimento estabelecido, foi realizada a implementação computacional, tendo em vista a elaboração de estudos com destaque às peculiaridades do fenômeno na presença de curtoscircuitos ao longo da linha de transmissão. Ambicionando ampliar as investigações da problemática ora em pauta e em sintonia com os objetivos pontuais do trabalho, foram realizadas simulações computacionais atreladas às variações das respectivas impedâncias de falta e à manifestação de eventuais desequilíbrios de tensão no sistema. Este conjunto de fatores de influência visaram, sobretudo, a constatação da robustez da metodologia diante de situações adversas, contrárias àquelas normalmente idealizadas em trabalhos precedentes. Os resultados evidenciaram, com clareza, o sucesso da metodologia, sobretudo, após a manifestação de faltas faseterra, as quais apresentaram menores valores de sobretensão e maiores percentuais de eficácia no processo do religamento. Por fim, diante das conclusões motivadoras, reconhecese que tal perspectiva aponta para efetivas possibilidades de aplicação do método em foco, o qual contribui para o aumento da confiabilidade dos sistemas elétricos. AGRADECIMENTOS Os autores agradecem ao CNPq e à CHESF pelo suporte financeiro ao trabalho e à Universidade Federal de Uberlândia (UFU) pela disponibilização dos recursos para a elaboração da pesquisa. REFERÊNCIAS [] CIGRE Working Group A3.07, Controlled Switching of HVAC Circuit Breakers, Benefits & Economic Aspects, Jan [2] P. Mestas, M. C. Tavares and A. M. Gole, "Implementation and Performance Evaluation of a Reclosing Method for Shunt Reactor Compensated Transmission Lines," IEEE Transactions on Power Delivery, vol. 26, no. 2, pp , Apr. 20. [3] A. D'ajuz, C. S. Fonseca, F. M. S. Carvalho, J. A. Filho, L. E. N. Dias, M. P. Pereira, P. C. V. Esmeraldo, R. Vaisman e S. d. O. Frontin, Transitórios Elétricos e Coordenação de Isolamentos Aplicação em Sistemas de Potência de AltaTensão, Rio de Janeiro: FURNAS, Universidade Federal Fluminense/EDUFF, 987. [4] J. K. Dillard, J. M. Clayton e L. A. Killard, Controlling Switching Surges on 00 kv Transmission Systems, IEEE Transaction on Power Apparatus and Systems, PAS89, pp , Nov [5] K. Ravishankar and D. Thukaram, "Control of Switching Surges due to Energization 765kV UHV Transmission Line," in IEEE 7th International Conference on Industrial and Information Systems (ICIIS), Chennai, India, Aug [6] A. Carvalho, M. Lacorte e O. Knudsen, Improved EHV Line Switching Surge Control by Application of MOarresters and Controlled Switching, International Conference on Energy Management and Power Delivery, vol., pp , Nov., 995. [7] CIGRE Task Force 3.00., Controlled Switching: A State of the Art Survey Part II, ELECTRA, n. 64, p. 39 6, Feb [8] H. Ito, Controlled Switching Technologies, StateoftheArt, Transmission and Distribution Conference and Exhibition 2002: Asia Pacific, IEEE/PES, [9] CIGRE Working Group 3.07, Controlled Switching of HVAC Circuit Breakers: Guide for Application Lines, Reactors, Capacitors, Transformers st Part, ELECTRA, n.83, pp. 4273, Apr [0] CIGRE Working Group 3.07, Controlled Switching of HVAC Circuit Breakers: Guide for Application Lines, Reactors, Capacitors, Transformers 2nd Part, ELECTRA, n. 85, pp. 3657, Aug [] ABB, Controlled Switching, Buyer's & Application Guide, 3rd ed. Ludvika, Sweden, Apr [2] K. Dantas, W. Neves and D. Fernandes, "An approach for controlled reclosing of shuntcompensated transmission lines," IEEE Transactions on Power Delivery, vol. 29, n. 3, p , Jun [3] K. M. C. Dantas, "Chaveamento Controlado Aplicado ao Religamento Rápido de Linhas de Transmissão," Tese (Doutorado), Universidade Federal de Campina Grande, Campina Grande, 202. [4] P. Gómez, Performance Evaluation of Time Domain Transmission Line Models for a Statistical Study of Switching Overvoltages, IEEE Latin America Transactions, vol., no. 4, pp , Sep [5] A. E. A. Araújo e W. L. A. Neves, Cálculo de Transitórios Eletromagnéticos em Sistemas de Energia, Belo Horizonte: Editora UFMG, [6] L. C. Zanetta Jr., Transitórios Eletromagnéticos em Sistemas de Potência, São Paulo SP: Editora da Universidade de São Paulo, [7] R. C. Silva e S. Kurokawa, Integration Methods Used in Numerical Simulations of Transient Electromagnetic, IEEE Latin America Transactions, vol. 9, no. 7, pp , Dec. 20. [8] T. Gönen, Electric Power Transmission System Engineering Analysis and Design. 2nd, Boca Raton, FL USA: CRC Press, [9] M. R. Spiegel, J. Schiller e R. A. Srinivasan, Probability and Statistics, New York USA: The McGrawHill Companies, Inc., 200. [20] R. C. F. Gregory, Análise Computacional do Desempenho de Estratégia para o Religamento Controlado de Linhas de Transmissão, Dissertação (Mestrado) Universidade Federal de Uberlândia, Uberlândia, 206. [2] L. V. Cunha, Desempenho de Linhas de Transmissão Frente a Descargas Atmosféricas: Influência do Efeito Corona na Ruptura a Meio de Vão, Dissertação (Mestrado), Universidade Federal de Minas Gerais, Belo Horizonte, 200. [22] ONS Operador Nacional do Sistema, Procedimentos de Rede Submódulo 2.8 Gerenciamento dos indicadores de qualidade da energia elétrica da Rede Básica, Dez [23] A. R. Hileman, Insulation Coordination for Power Systems, New York USA: Marcel Dekker, Inc., 999.

8 FILIAGI GREGORY et al.: PERFORMANCE ANALYSIS Raquel Cristina Filiagi Gregory é engenheira eletricista (204) pela Universidade Federal de Mato Grosso (UFMT) e mestre (206) em Engenharia Elétrica pela Universidade Federal de Uberlândia (UFU). Atualmente é aluna de doutorado da Universidade Federal de Uberlândia e sua principal área de interesse é em sistemas elétricos de potência com ênfase em qualidade da energia elétrica. Andréia Crico dos Santos é engenheira eletricista (203) e mestre (205) em Engenharia Elétrica pela Universidade Federal de Uberlândia (UFU). Atualmente é doutoranda nesta mesma universidade e professora do Instituto Federal de Educação, Ciência e Tecnologia do Triângulo Mineiro (IFTM). Suas principais áreas de interesse são qualidade da energia elétrica e geração distribuída. José Carlos de Oliveira é engenheiro eletricista (970) e mestre (974) em Engenharia Elétrica, ambos pela Universidade Federal de Itajubá, e doutor (978) em Engenharia Elétrica pela University of Manchester Institute of Science Technology, Manchester, GB. Atualmente é professor da Faculdade Engenharia Elétrica da Universidade Federal de Uberlândia. Sua principal área de interesse é em sistemas elétricos de potência com ênfase em qualidade da energia elétrica. Marcelo Lynce Ribeiro Chaves é engenheiro eletricista (975) e mestre (987) em Engenharia Elétrica pela Universidade Federal de Uberlândia (UFU). Possui doutorado (995) em Engenharia Elétrica pela Universidade Estadual de Campinas (Unicamp). Atualmente é professor da Universidade Federal de Uberlândia e sua principal área de interesse é em sistemas elétricos de potência. Karcius Marcelus Colaço Dantas é engenheiro eletricista (2005) e mestre (2007) e doutor (202) em Engenharia Elétrica pela Universidade Federal de Campina Grande (UFCG). Atualmente é professor da Universidade Federal de Campina Grande e sua principal área de interesse é em transitórios eletromagnéticos em sistemas elétricos e qualidade da energia elétrica. 7 Washington Luiz Araújo Neves é engenheiro eletricista (979) e mestre (982) em Engenharia Elétrica pela Universidade Federal da Paraíba (UFPB). Possui doutorado (994) em Engenharia Elétrica pela University of British Columbia (UBC). Atualmente é professor da UFCG e sua principal área de interesse é em transitórios eletromagnéticos em sistemas elétricos e qualidade da energia elétrica. Damásio Fernandes Júnior é engenheiro eletricista (997) e mestre (999) em Engenharia Elétrica pela Universidade Federal da Paraíba (UFPB). Possui doutorado (2004) em Engenharia Elétrica pela Universidade Federal de Campina Grande (UFCG). Atualmente é professor da UFCG e sua principal área de interesse é em transitórios e métodos de otimização para aplicação em sistemas de energia. Luiz Carlos de Alcântara Fonseca é engenheiro eletricista (977) e mestre (2003) em Sistemas de Potência pela Universidade Federal de Pernambuco (UFPE). Atualmente trabalha no Departamento de Planejamento do Sistema de Transmissão da Companhia Hidro Elétrica do São Francisco (CHESF) e suas áreas de interesse são em compatibilidade eletromagnética transitórios eletromagnéticos e qualidade da energia elétrica.

MODELING AND PERFORMANCE ANALYSIS OF TRANSMISSION LINES RECLOSING STRATEGY FOR TRANSIENT MITIGATION VIA CONTROLLED SWITCHING

MODELING AND PERFORMANCE ANALYSIS OF TRANSMISSION LINES RECLOSING STRATEGY FOR TRANSIENT MITIGATION VIA CONTROLLED SWITCHING MODELAGEM E ANÁLISE DE DESEMPENHO DE ESTRATÉGIA PARA MITIGAÇÃO DE TRANSITÓRIOS DE RELIGAMENTO DE LINHAS DE TRANSMISSÃO ATRAVÉS DE CHAVEAMENTO CONTROLADO Raquel C. F. Gregory¹, Andréia C. dos Santos¹, José

Leia mais

Detecção da Extinção de Defeitos em Linhas de Transmissão para Religamento Trifásico

Detecção da Extinção de Defeitos em Linhas de Transmissão para Religamento Trifásico 1 Detecção da Extinção de Defeitos em Linhas de Transmissão para Religamento Trifásico Karcius M. C. Dantas, Washington L. A. Neves e Damásio Fernandes Jr. Resumo No SIN (Sistema Interligado Nacional),

Leia mais

Identificação da Extinção de Defeitos Aplicado a Linhas de Transmissão de Circuito Duplo

Identificação da Extinção de Defeitos Aplicado a Linhas de Transmissão de Circuito Duplo Identificação da Extinção de Defeitos Aplicado a Linhas de Transmissão de Circuito Duplo Karcius Marcelus Colaço Dantas, Nathalia de Morais Dias Campos Resumo O objetivo deste trabalho é avaliar o desempenho

Leia mais

ESTUDO COMPARATIVO DE MÉTODOS DE REDUÇÃO DE SOBRETENSÕES TRANSITÓRIAS EM LINHAS DE TRANSMISSÃO

ESTUDO COMPARATIVO DE MÉTODOS DE REDUÇÃO DE SOBRETENSÕES TRANSITÓRIAS EM LINHAS DE TRANSMISSÃO ESTUDO COMPARATIVO DE MÉTODOS DE REDUÇÃO DE SOBRETENSÕES TRANSITÓRIAS EM LINHAS DE TRANSMISSÃO Daphne D. L. T. Barros daphne.barros@ee.com.br Universidade Federal de Campina Grande Av. Aprígio de Veloso,

Leia mais

Chaveamento Controlado de Linhas de Transmissão

Chaveamento Controlado de Linhas de Transmissão Chaveamento Controlado de Linhas de Transmissão Karcius M. C. Dantas, Washington L. A. Neves, Damásio Fernandes Jr., Benemar A. Souza, e Luiz C. Fonseca 1 Resumo Um método para chaveamento controlado de

Leia mais

XX SNPTEE SEMINÁRIO NACIONAL DE PRODUÇÃO E TRANSMISSÃO DE ENERGIA ELÉTRICA GRUPO X GRUPO DE ESTUDOS DE DESEMPENHO DE SISTEMAS ELÉTRICOS - GDS

XX SNPTEE SEMINÁRIO NACIONAL DE PRODUÇÃO E TRANSMISSÃO DE ENERGIA ELÉTRICA GRUPO X GRUPO DE ESTUDOS DE DESEMPENHO DE SISTEMAS ELÉTRICOS - GDS XX SNPTEE SEMINÁRIO NACIONAL DE PRODUÇÃO E TRANSMISSÃO DE ENERGIA ELÉTRICA Versão 1. XXX.YY 22 a 25 Novembro de 29 Recife - PE GRUPO X GRUPO DE ESTUDOS DE DESEMPENHO DE SISTEMAS ELÉTRICOS - GDS CONTROLE

Leia mais

XX SNPTEE SEMINÁRIO NACIONAL DE PRODUÇÃO E TRANSMISSÃO DE ENERGIA ELÉTRICA GRUPO - X GRUPO DE ESTUDOS DE DESEMPENHO DE SISTEMAS ELÉTRICOS GDS

XX SNPTEE SEMINÁRIO NACIONAL DE PRODUÇÃO E TRANSMISSÃO DE ENERGIA ELÉTRICA GRUPO - X GRUPO DE ESTUDOS DE DESEMPENHO DE SISTEMAS ELÉTRICOS GDS XX SNPTEE SEMINÁRIO NACIONAL DE PRODUÇÃO E TRANSMISSÃO DE ENERGIA ELÉTRICA Versão. XXX.YY 22 a 25 Novembro de 29 Recife - PE GRUPO - X GRUPO DE ESTUDOS DE DESEMPENHO DE SISTEMAS ELÉTRICOS GDS UMA CHAVE

Leia mais

Análise das solicitações impostas ao banco de capacitores devido à energização e manobras dos disjuntores

Análise das solicitações impostas ao banco de capacitores devido à energização e manobras dos disjuntores Análise das solicitações impostas ao banco de capacitores devido à energização e manobras dos disjuntores Este Relatório Técnico apresenta os estudos das solicitações impostas ao banco de capacitores 88/138

Leia mais

Avaliação de sobretensões em subestações isoladas a SF6 interconectadas por cabos

Avaliação de sobretensões em subestações isoladas a SF6 interconectadas por cabos 38 Capítulo XII Avaliação de sobretensões em subestações isoladas a SF6 interconectadas por cabos Por Rafael Azevedo, José Geraldo de Andrade e Marta Lacorte* A expansão do sistema elétrico para atendimento

Leia mais

SNPTEE SEMINÁRIO NACIONAL DE PRODUÇÃO E TRANSMISSÃO DE ENERGIA ELÉTRICA

SNPTEE SEMINÁRIO NACIONAL DE PRODUÇÃO E TRANSMISSÃO DE ENERGIA ELÉTRICA SNPTEE SEMINÁRIO NACIONAL DE PRODUÇÃO E TRANSMISSÃO DE ENERGIA ELÉTRICA GSC 14 a 17 Outubro de 007 Rio de Janeiro - RJ GRUPO X GRUPO DE ESTUDO DE SOBRETENSÕES E COORDINAÇÃO DE ISOLAMENTO - GSC ANÁLISE

Leia mais

Estudo de Surtos Decorrentes de Manobras em Bancos de Capacitores Procedimentos Computacionais

Estudo de Surtos Decorrentes de Manobras em Bancos de Capacitores Procedimentos Computacionais Estudo de Surtos Decorrentes de Manobras em Bancos de Capacitores Procedimentos Computacionais e Medidas Mitigadoras Danielly Formiga P. de Moura, Karcius Marcelus C. Dantas, Washington L. A. Neves e Damásio

Leia mais

ANÁLISE DO DESEMPENHO DA PROTEÇÃO DIFERENCIAL SOB CONDIÇÃO DE SATURAÇÃO DOS TRANSFORMADORES DE CORRENTE

ANÁLISE DO DESEMPENHO DA PROTEÇÃO DIFERENCIAL SOB CONDIÇÃO DE SATURAÇÃO DOS TRANSFORMADORES DE CORRENTE ANÁLISE DO DESEMPENHO DA PROTEÇÃO DIFERENCIAL SOB CONDIÇÃO DE SATURAÇÃO DOS TRANSFORMADORES DE CORRENTE Code: 19.031 Arian Fagundes, Alex Itczak, Eduardo Machado dos Santos, John J. Saldanha, Marcel Stalter,

Leia mais

Devido à necessidade da correção

Devido à necessidade da correção INSTALAÇÕES SERVIÇO INDUSTRIAIS Estudo de mitigação de transitórios de chaveamento de capacitores Glássio Costa de Miranda, da Universidade Federal de Minas Gerais, e Henrique Fantoni Primo, da SM&A Sistemas

Leia mais

MODELAGEM PARA SIMULAÇÃO EM TEMPO REAL DE UM CONVERSOR CA-CC

MODELAGEM PARA SIMULAÇÃO EM TEMPO REAL DE UM CONVERSOR CA-CC MODELAGEM PARA SIMULAÇÃO EM TEMPO REAL DE UM CONVERSOR CA-CC Raoni de Araújo Pegado 1 ; Karcius Marcelus Colaço Dantas 2. 1 Aluno da Universidade Federal de Campina Grande, raoni.pegado@ee.ufcg.edu.br;

Leia mais

Integration Methods Used in Numerical Simulations of Electromagnetic Transients

Integration Methods Used in Numerical Simulations of Electromagnetic Transients 16 IEEE LATIN AMERICA TRANSACTIONS, VOL. 9, NO. 7, DECEMBER 211 Integration Methods Used in Numerical Simulations of Electromagnetic Transients R. C. Silva, Student Member, IEEE, S. Kurokawa, Member Abstract

Leia mais

Décimo Quinto Encontro Regional Ibero-americano do CIGRÉ Foz do Iguaçu-PR, Brasil 19 a 23 de maio de 2013

Décimo Quinto Encontro Regional Ibero-americano do CIGRÉ Foz do Iguaçu-PR, Brasil 19 a 23 de maio de 2013 UM MÉTODO PRÁTICO PARA REPRESENTAÇÃO DE TRANSFORMADORES DE POTÊNCIA BASEADO EM MEDIÇÕES DE RESPOSTA EM FREQUÊNCIA Rogério Magalhães de Azevedo Marcelo Guimarães Rodrigues Walter Cerqueira CEPEL RESUMO

Leia mais

Análise das solicitações impostas ao banco de capacitores devido à energização e manobras dos disjuntores

Análise das solicitações impostas ao banco de capacitores devido à energização e manobras dos disjuntores Análise das solicitações impostas ao banco de capacitores devido à energização e manobras dos disjuntores Este Relatório Técnico apresenta os estudos das solicitações impostas ao banco de capacitores 88/138

Leia mais

ANÁLISE DA OPERAÇÃO DE UMA LINHA DE TRANSMISSÃO DE ALTA TENSÃO COM CIRCUITO DUPLO EM REGIME PERMANENTE E NA OCORRÊNCIA DE UMA FALTA MONOFÁSICA

ANÁLISE DA OPERAÇÃO DE UMA LINHA DE TRANSMISSÃO DE ALTA TENSÃO COM CIRCUITO DUPLO EM REGIME PERMANENTE E NA OCORRÊNCIA DE UMA FALTA MONOFÁSICA ANÁLISE DA OPERAÇÃO DE UMA LINHA DE TRANSMISSÃO DE ALTA TENSÃO COM CIRCUITO DUPLO EM REGIME PERMANENTE E NA OCORRÊNCIA DE UMA FALTA MONOFÁSICA Vinicius C. de Paula, Isaque N. Gondim, Marcelo L. R. Chaves,

Leia mais

Compensador Estático de Reativos Controlado a Tiristores: Modelagem e Simulação

Compensador Estático de Reativos Controlado a Tiristores: Modelagem e Simulação 1 Compensador Estático de Reativos Controlado a Tiristores: Modelagem e Simulação J. C. de Oliveira, PhD; A. B. de Vasconcellos, Dr.; R. Apolônio, Dr.; M. K. Kawaphara, Dr.; J. E. Carvalho, Eng o e E.

Leia mais

TRATAMENTO DE SOLICITAÇÕES TRANSITÓRIAS SOBRE REATORES DE POTÊNCIA DE EAT - UTILIZAÇÃO DA MANOBRA CONTROLADA NÃO CONVENCIONAL

TRATAMENTO DE SOLICITAÇÕES TRANSITÓRIAS SOBRE REATORES DE POTÊNCIA DE EAT - UTILIZAÇÃO DA MANOBRA CONTROLADA NÃO CONVENCIONAL SNPTEE SEMINÁRIO NACIONAL DE PRODUÇÃO E TRANSMISSÃO DE ENERGIA ELÉTRICA GSC - 16 16 a 21 Outubro de 2005 Curitiba - Paraná GRUPO X GRUPO ESTUDOS DE SOBRETENSÕES E COORDENAÇÃO DE ISOLAMENTO - GSC TRATAMENTO

Leia mais

SOBRETENSÕES TRANSITÓRIAS DECORRENTES DE MANOBRAS DE BANCOS DE CAPACITORES

SOBRETENSÕES TRANSITÓRIAS DECORRENTES DE MANOBRAS DE BANCOS DE CAPACITORES SOBRETENSÕES TRANSITÓRIAS DECORRENTES DE MANOBRAS DE BANCOS DE CAPACITORES F. M. P. Pamplona, D. Fernandes Jr., B. A. Souza, W. L. A. Neves Laboratório de Alta Tensão, Departamento de Engenharia Elétrica,

Leia mais

Transitórios Por Gilson Paulillo, Mateus Duarte Teixeira e Ivandro Bacca*

Transitórios Por Gilson Paulillo, Mateus Duarte Teixeira e Ivandro Bacca* 42 Capítulo XI Transitórios Por Gilson Paulillo, Mateus Duarte Teixeira e Ivandro Bacca* O termo transitório tem sido aplicado à análise da tensão e/ou corrente, sendo unidirecional na sua das variações

Leia mais

GABRIEL DEL SANTORO BRESSAN INTRODUÇÃO AOS ESTUDOS DE CURTO-CIRCUITO

GABRIEL DEL SANTORO BRESSAN INTRODUÇÃO AOS ESTUDOS DE CURTO-CIRCUITO GABRIEL DEL SANTORO BRESSAN INTRODUÇÃO AOS ESTUDOS DE CURTO-CIRCUITO SINOP/MT 2016 INTRODUÇÃO O estudo de curtos-circuitos representa vital importância para a proteção de sistemas elétricos, tendo em vista

Leia mais

DESEQUILÍBRIO DE TENSÕES EM INSTALAÇÕES ELÉTRICAS AGROINDUSTRIAIS

DESEQUILÍBRIO DE TENSÕES EM INSTALAÇÕES ELÉTRICAS AGROINDUSTRIAIS DESEQUILÍBRIO DE TENSÕES EM INSTALAÇÕES ELÉTRICAS AGROINDUSTRIAIS Ricardo Martini Rodrigues [1] Paulo José Amaral Serni [2] José Francisco Rodrigues [3] Luiz Gonzaga Campos Porto [4] Departamento de Engenharia

Leia mais

Configuração Ótima para Manobra de Equipamentos Elétricos de Potência via Análise no Domínio da Freqüência

Configuração Ótima para Manobra de Equipamentos Elétricos de Potência via Análise no Domínio da Freqüência 1 Configuração Ótima para Manobra de Equipamentos Elétricos de Potência via Análise no Domínio da Freqüência Alécio B. Fernandes, Member, IEEE, e Roberval M. da Silva Resumo--Freqüentemente, nos estudos

Leia mais

Décimo Quinto Encontro Regional Ibero-americano do CIGRÉ Foz do Iguaçu-PR, Brasil 19 a 23 de maio de 2013

Décimo Quinto Encontro Regional Ibero-americano do CIGRÉ Foz do Iguaçu-PR, Brasil 19 a 23 de maio de 2013 DETERMINAÇÃO DOS PARÂMETROS DO CIRCUITO PRINCIPAL DE COMPENSADORES ESTÁTICOS INSTALADOS PARA INTEGRAÇÃO AO SISTEMA INTERLIGADO BRASILEIRO DE PARQUES EÓLICOS: O EXEMPLO DO CE EXTREMOZ Manfredo Correia Lima

Leia mais

LABORATÓRIO DE SISTEMAS DE POTÊNCIA EXPERIÊNCIA: CURTO-CIRCUITO RELATÓRIO. Alunos: 1)... 2)... Professor:... Data:...

LABORATÓRIO DE SISTEMAS DE POTÊNCIA EXPERIÊNCIA: CURTO-CIRCUITO RELATÓRIO. Alunos: 1)... 2)... Professor:... Data:... LABORATÓRIO DE SISTEMAS DE POTÊNCIA EXPERIÊNCIA: CURTO-CIRCUITO - 2013 RELATÓRIO NOTA... Alunos: 1)... 2)... Professor:... Data:..... 1. OBJETIVOS DA EXPERIÊNCIA Aplicação de programas de curto-circuito;

Leia mais

SOLUÇÕES EM QUALIDADE DE ENERGIA Soluções em média e alta tensão

SOLUÇÕES EM QUALIDADE DE ENERGIA Soluções em média e alta tensão SOLUÇÕES EM QUALIDADE DE ENERGIA Soluções em média e alta tensão 2 Moving together 1. PAINÉIS METÁLICOS, FILTROS DE HARMÔNICOS E BANCOS DE CAPACITORES 1. PAINÉIS METÁLICOS, FILTROS DE HARMÔNICOS E BANCOS

Leia mais

Capítulo IV Aplicação de Filtros Harmônicos Passivos LC e Eletromagnéticos em Sistemas de Distribuição

Capítulo IV Aplicação de Filtros Harmônicos Passivos LC e Eletromagnéticos em Sistemas de Distribuição Adicionalmente, as figuras (4.4) e (4.5) mostram, respectivamente, o perfil de tensão de fase e corrente de neutro obtidos nas medições em um dia típico. 1,10 1,08 Fase A Fase B Fase C 1,06 1,04 1,02 1,00

Leia mais

XVIII Seminário Nacional de Distribuição de Energia Elétrica. Aplicação de Disjuntores em Geradores de Média Potência

XVIII Seminário Nacional de Distribuição de Energia Elétrica. Aplicação de Disjuntores em Geradores de Média Potência XVIII Seminário Nacional de Distribuição de Energia Elétrica Olinda - Pernambuco - Brasil SENDI 2008-06 a 10 de outubro Aplicação de Disjuntores em Geradores de Média Potência Lucilius C. Pinto Marcelo

Leia mais

CHAVEAMENTO CONTROLADO DE LINHAS DE TRANSMISSÃO: UMA ABORDAGEM EM TEMPO REAL VIA RTDS TM

CHAVEAMENTO CONTROLADO DE LINHAS DE TRANSMISSÃO: UMA ABORDAGEM EM TEMPO REAL VIA RTDS TM CHAVEAMENTO CONTROLADO DE LINHAS DE TRANSMISSÃO: UMA ABORDAGEM EM TEMPO REAL VIA RTDS TM Karcius Marcelus Colaço Dantas karcius@dee.ufcg.edu.br Damásio Fernandes Jr. damasio@dee.ufcg.edu.br Luiz Carlos

Leia mais

1. Introdução ao Estudo de Equipamentos Elétricos Os estudos básicos visando à especificação das características dos equipamentos, realizados na

1. Introdução ao Estudo de Equipamentos Elétricos Os estudos básicos visando à especificação das características dos equipamentos, realizados na 1. Introdução ao Estudo de Equipamentos Elétricos Os estudos básicos visando à especificação das características dos equipamentos, realizados na etapa de detalhamento, consistem no estudo de fluxo de potência,

Leia mais

SNPTEE SEMINÁRIO NACIONAL DE PRODUÇÃO E TRANSMISSÃO DE ENERGIA ELÉTRICA GRUPO X GRUPO DE ESTUDO DE SOBRETENSÕES E COORDENAÇÃO DE ISOLAMENTO - GSC

SNPTEE SEMINÁRIO NACIONAL DE PRODUÇÃO E TRANSMISSÃO DE ENERGIA ELÉTRICA GRUPO X GRUPO DE ESTUDO DE SOBRETENSÕES E COORDENAÇÃO DE ISOLAMENTO - GSC SNPTEE SEMINÁRIO NACIONAL DE PRODUÇÃO E TRANSMISSÃO DE ENERGIA ELÉTRICA GSC 24 14 a 17 Outubro de 2007 Rio de Janeiro - RJ GRUPO X GRUPO DE ESTUDO DE SOBRETENSÕES E COORDENAÇÃO DE ISOLAMENTO - GSC ANÁLISE

Leia mais

Relé de Sincronismo. Promotor de Power Quality em T&D. André R. Totti. ABB HV Products - Page 1. (11) ABB

Relé de Sincronismo. Promotor de Power Quality em T&D. André R. Totti. ABB HV Products - Page 1. (11) ABB Relé de Sincronismo Promotor de Power Quality em T&D HV Products - Page 1 André R. Totti andre.totti@br.abb.com (11) 6464-8195 Relé de Sincronismo: Power Quality em T&D A qualidade de energia é afetada

Leia mais

a 11/07/17 SOM DHVL AMP RDA Arquivo. REV. DATA PREP. VERIF. VISTO APROV. DESCRIÇÃO CEMIG GERAÇÃO E TRANSMISSÃO S.A. Sistema Elétrico SE SÃO SIMÃO

a 11/07/17 SOM DHVL AMP RDA Arquivo. REV. DATA PREP. VERIF. VISTO APROV. DESCRIÇÃO CEMIG GERAÇÃO E TRANSMISSÃO S.A. Sistema Elétrico SE SÃO SIMÃO DISTR. QTDE/TIPO ORGÃO DISTRIBUIÇÃO AUTOMÁTICA DE CÓPIAS TOTAL a 11/07/17 SOM DHVL AMP RDA Arquivo. REV. DATA PREP. VERIF. VISTO APROV. DESCRIÇÃO RESERVADO CONT. CLASSIFICAÇÃO ELABORADO POR: VISTO POR:

Leia mais

Estudos Complementares para Avaliação de Transitórios Associados à Operação de Bancos de Capacitores Série em 500kV

Estudos Complementares para Avaliação de Transitórios Associados à Operação de Bancos de Capacitores Série em 500kV 1 Estudos Complementares para Avaliação de Transitórios Associados à Operação de Bancos de Capacitores Série em 500kV Manfredo Correia Lima, Fernando Rodrigues Alves, Sebastian Henschel, Lutz Kirschner

Leia mais

V SBQEE. Seminário Brasileiro sobre Qualidade da Energia Elétrica 17 a 20 de Agosto de 2003 Aracaju Sergipe Brasil

V SBQEE. Seminário Brasileiro sobre Qualidade da Energia Elétrica 17 a 20 de Agosto de 2003 Aracaju Sergipe Brasil V SBQEE Seminário Brasileiro sobre Qualidade da Energia Elétrica 17 a 2 de Agosto de 23 Aracaju Sergipe Brasil Código: AJU 4 115 Tópico: Análise, Diagnósticos e Soluções ANÁLISE DA INFLUÊNCIA DO ATERRAMENTO

Leia mais

MODELAGEM E SIMULAÇÃO DE FUNÇÕES DE PROTEÇÃO ELÉTRICA DE PEQUENAS CENTRAIS HIDRELÉTRICAS (PCHS) UTILIZANDO O SOFTWARE ATP/ATPDraw

MODELAGEM E SIMULAÇÃO DE FUNÇÕES DE PROTEÇÃO ELÉTRICA DE PEQUENAS CENTRAIS HIDRELÉTRICAS (PCHS) UTILIZANDO O SOFTWARE ATP/ATPDraw Engenharias - Engenharia Elétrica - Medidas Elétricas, Magnéticas e Eletrônicas; Instrumentação - Sistemas Eletrônicos de Medida e de Controle (Engenharia IV) MODELAGEM E SIMULAÇÃO DE FUNÇÕES DE PROTEÇÃO

Leia mais

LISTA DE ILUSTRAÇÕES

LISTA DE ILUSTRAÇÕES LISTA DE ILUSTRAÇÕES Figura 1.1 Modelo bidirecional de queda de tensão... 07 Figura 1.2 Diagrama esquemático das três possibilidades de paralelismo de alimentadores aéreos... 09 Figura 1.3 Alimentador

Leia mais

GRUPO X GRUPO DE ESTUDO DE SOBRETENSÕES E COORDENAÇÃO DE ISOLAMENTO - GSC

GRUPO X GRUPO DE ESTUDO DE SOBRETENSÕES E COORDENAÇÃO DE ISOLAMENTO - GSC SNPTEE SEMINÁRIO NACIONAL DE PRODUÇÃO E TRANSMISSÃO DE ENERGIA ELÉTRICA GSC - 29 16 a 21 Outubro de Curitiba - Paraná GRUPO X GRUPO DE ESTUDO DE SOBRETENSÕES E COORDENAÇÃO DE ISOLAMENTO - GSC ESTUDO DE

Leia mais

Introdução a proteção de redes ativas de distribuição em CC

Introdução a proteção de redes ativas de distribuição em CC Introdução a proteção de redes ativas de distribuição em CC Eletrônica de Potência para Redes Ativas de Distribuição Refs.: Per Karlsson, DC Distributed Power Systems - Analysis, Design and Control for

Leia mais

Controle & Automação vol.14 no.1 Mar. 2003

Controle & Automação vol.14 no.1 Mar. 2003 CONVERSORES DE FREQUÊNCIA VSI-PWM SUBMETIDOS A AFUNDAMENTOS TEMPORÁRIOS DE TENSÃO ( VOLTAGE SAGS ) Autores do artigo: Paulo C. A. Leão (Departamento de Engenharia Elétrica Universidade Federal de São João

Leia mais

Capítulo 3. Modelagem da Rede Elétrica Estudada

Capítulo 3. Modelagem da Rede Elétrica Estudada Modelagem da Rede Elétrica Estudada 58 3 MODELAGEM DA REDE ELÉTRICA ESTUDADA. A primeira fase do estudo foi a escolha da subestação e dos alimentadores aéreos primários. A subestação, bem como seus circuitos

Leia mais

Wellter M. Sozin*¹, Leandro P. Moura¹, Thássio M. Pereira¹, Maria C. D. Tavares¹, Joan S. Chaves H.¹

Wellter M. Sozin*¹, Leandro P. Moura¹, Thássio M. Pereira¹, Maria C. D. Tavares¹, Joan S. Chaves H.¹ INFLUÊNCIA DA PERMEABILIDADE MAGNÉTICA RELATIVA DOS CABOS PARA-RAIOS NOS PARÂMETROS ELÉTRICOS DAS LINHAS DE TRANSMISSÃO E NOS TRANSITÓRIOS ELETROMAGNÉTICOS Wellter M. Sozin*¹, Leandro P. Moura¹, Thássio

Leia mais

Universidade de Brasília - UnB Faculdade UnB Gama - FGA Curso de Engenharia de Energia

Universidade de Brasília - UnB Faculdade UnB Gama - FGA Curso de Engenharia de Energia 0 Universidade de Brasília - UnB Faculdade UnB Gama - FGA Curso de Engenharia de Energia ANÁLISE DE ENERGIZAÇÃO E RELIGAMENTO DE LINHA DE TRANSMISSÃO NO SOFTWARE ATP Autor: Guilherme Beloti Soares Orientador:

Leia mais

Palavras-chave: distribuição de energia elétrica; fluxo de potência; regulador de tensão.

Palavras-chave: distribuição de energia elétrica; fluxo de potência; regulador de tensão. Desenvolvimento e Modelagem de Regulador de Tensão para Fluxo de Potência em Redes de Distribuição de Energia Elétrica Rodrigo Mendonça de CARVALHO; Antônio Cesar Baleeiro ALVES Escola de Engenharia Elétrica

Leia mais

REDUÇÃO DAS CORRENTES DE ARCO SECUNDÁRIO EM SISTEMAS DE TRANSMISSÃO TÍPICOS

REDUÇÃO DAS CORRENTES DE ARCO SECUNDÁRIO EM SISTEMAS DE TRANSMISSÃO TÍPICOS REDUÇÃO DAS CORRENTES DE ARCO SECUNDÁRIO EM SISTEMAS DE TRANSMISSÃO TÍPICOS Milton E. Zevallos zevallos@dsce.fee.unicamp.br Maria C. Tavares cristina@dsce.fee.unicamp.br DSCE, FEEC, UNICAMP. Caixa Postal

Leia mais

V SBQEE CARACTERÍSTICAS DE DESEMPENHO OPERACIONAL DO SISTEMA SUPRIDOR A CONSUMIDORES INDUSTRIAIS

V SBQEE CARACTERÍSTICAS DE DESEMPENHO OPERACIONAL DO SISTEMA SUPRIDOR A CONSUMIDORES INDUSTRIAIS V SBQEE Seminário Brasileiro sobre Qualidade da Energia Elétrica 17 a 20 de Agosto de 2003 Aracaju Sergipe Brasil Código: AJU 04 173 Tópico: Análise, Diagnósticos e Soluções CARACTERÍSTICAS DE DESEMPENHO

Leia mais

Universidade de Brasília - UnB Faculdade UnB Gama - FGA Curso de Engenharia de Energia ANÁLISE DE ENERGIZAÇÃO DE LINHAS DE TRANSMISSÃO

Universidade de Brasília - UnB Faculdade UnB Gama - FGA Curso de Engenharia de Energia ANÁLISE DE ENERGIZAÇÃO DE LINHAS DE TRANSMISSÃO 0 Universidade de Brasília - UnB Faculdade UnB Gama - FGA Curso de Engenharia de Energia ANÁLISE DE ENERGIZAÇÃO DE LINHAS DE TRANSMISSÃO Autor: Guilherme Beloti Soares Orientador: Prof. Dr. Alex Reis Brasília,

Leia mais

TUTORIAL. Agregação de Eventos de Variação de Tensão de Curta Duração. Prof. Dr. José Rubens Macedo Jr. Revisão 4 Agosto/2017

TUTORIAL. Agregação de Eventos de Variação de Tensão de Curta Duração. Prof. Dr. José Rubens Macedo Jr. Revisão 4 Agosto/2017 TUTORIAL Agregação de Eventos de Variação de Tensão de Curta Duração Revisão 4 Agosto/2017 Prof. Dr. José Rubens Macedo Jr. Contribuíram para a revisão deste Tutorial: Prof. Dr. José Carlos de Oliveira

Leia mais

GRUPO XIII GRUPO DE ESTUDO DE INTERFERÊNCIAS, COMPATIBILIDADE ELETROMAGNÉTICA E QUALIDADE DE ENERGIA - GCQ

GRUPO XIII GRUPO DE ESTUDO DE INTERFERÊNCIAS, COMPATIBILIDADE ELETROMAGNÉTICA E QUALIDADE DE ENERGIA - GCQ SNPTEE SEMINÁRIO NACIONAL DE PRODUÇÃO E TRANSMISSÃO DE ENERGIA ELÉTRICA GCQ - 19 16 a 21 Outubro de 2005 Curitiba - Paraná GRUPO XIII GRUPO DE ESTUDO DE INTERFERÊNCIAS, COMPATIBILIDADE ELETROMAGNÉTICA

Leia mais

XXIV SNPTEE SEMINÁRIO NACIONAL DE PRODUÇÃO E TRANSMISSÃO DE ENERGIA ELÉTRICA. 22 a 25 de outubro de 2017 Curitiba - PR

XXIV SNPTEE SEMINÁRIO NACIONAL DE PRODUÇÃO E TRANSMISSÃO DE ENERGIA ELÉTRICA. 22 a 25 de outubro de 2017 Curitiba - PR XXIV SNPTEE SEMINÁRIO NACIONAL DE PRODUÇÃO E TRANSMISSÃO DE ENERGIA ELÉTRICA CB/GDS/08 22 a 25 de outubro de 2017 Curitiba - PR GRUPO - X GRUPO DE ESTUDO DE DESEMPENHO DE SISTEMAS ELÉTRICOS - GDS MODELAGEM

Leia mais

A Figura VIII.7 representa, esquematicamente, o transformador de potencial. Figura VIII.7 - Transformador de Potencial

A Figura VIII.7 representa, esquematicamente, o transformador de potencial. Figura VIII.7 - Transformador de Potencial VIII.3 - TRANFORMADOR DE OTENCIAL (T) VIII.3.1 - GENERALIDADE A Figura VIII.7 representa, esquematicamente, o transformador de potencial. - ITEMA + ITEMA I + - RT + - I Z Figura VIII.7 - Transformador

Leia mais

SNPTEE SEMINÁRIO NACIONAL DE PRODUÇÃO E TRANSMISSÃO DE ENERGIA ELÉTRICA GRUPO X GRUPO DE ESTUDO DESOBRETENSÕES E COORDENAÇÃO DE ISOLAMENTO GSC

SNPTEE SEMINÁRIO NACIONAL DE PRODUÇÃO E TRANSMISSÃO DE ENERGIA ELÉTRICA GRUPO X GRUPO DE ESTUDO DESOBRETENSÕES E COORDENAÇÃO DE ISOLAMENTO GSC SNPTEE SEMINÁRIO NACIONAL DE PRODUÇÃO E TRANSMISSÃO DE ENERGIA ELÉTRICA GSC 21 14 a 17 Outubro de 7 Rio de Janeiro - RJ GRUPO X GRUPO DE ESTUDO DESOBRETENSÕES E COORDENAÇÃO DE ISOLAMENTO GSC AVALIAÇÃO

Leia mais

ATUAÇÃO DE PROTEÇÃO DE SOBRECORRENTE DEVIDO FALTAS A TERRA EM SISTEMAS ISOLADOS

ATUAÇÃO DE PROTEÇÃO DE SOBRECORRENTE DEVIDO FALTAS A TERRA EM SISTEMAS ISOLADOS GSI Nº: ART055-09 - CD 382-09 ATUAÇÃO DE PROTEÇÃO DE SOBRECORRENTE DEVIDO FALTAS A TERRA EM SISTEMAS ISOLADOS João Roberto Cogo Artigo publicado na Revista Eletricidade Moderna - Ano XXVII, nº 302 - Maio

Leia mais

Tipos de Curtos-Circuitos

Tipos de Curtos-Circuitos Tipos de Curtos-Circuitos Prof. Dr. Eduardo Coelho Marques da Costa Escola Politécnica da Universidade de São Paulo Graduação em Engenharia Elétrica Conteúdo Definição Causas Ocorrência Consequências Importância

Leia mais

MODELAGEM DO CIRCUITO DE ENSAIO DE GERAÇÃO DE ARCO ELÉTRICO NO ATP

MODELAGEM DO CIRCUITO DE ENSAIO DE GERAÇÃO DE ARCO ELÉTRICO NO ATP Puerto Iguazú Argentina XIII ERIAC DÉCIMO TERCER ENCUENTRO REGIONAL IBEROAMERICANO DE CIGRÉ 24 al 28 de mayo de 29 Comité de Estudio C4 - Desempeño Técnico del Sistema XIII/PI-C4-6 MODELAGEM DO CIRCUITO

Leia mais

PROCESSO DE PROJETO E CONSTRUÇÃO SUBPROCESSO DE INSTALAÇÃO ELÉTRICA DE CONSUMIDOR

PROCESSO DE PROJETO E CONSTRUÇÃO SUBPROCESSO DE INSTALAÇÃO ELÉTRICA DE CONSUMIDOR PROCESSO DE PROJETO E CONSTRUÇÃO SUBPROCESSO DE INSTALAÇÃO ELÉTRICA DE CONSUMIDOR 1. OBJETIVO Estabelecer critérios para projeto de melhoria do fator de potência nas instalações elétricas das unidades

Leia mais

Figura Circuito para determinação da seqüência de fases

Figura Circuito para determinação da seqüência de fases A C B R N C R N Figura 4.1 - Circuito para determinação da seqüência de fases Exercício 4.2 No circuito da Figura 4.2, quando ocorre um defeito fase-terra franco na barra P, pede-se determinar: a) a corrente

Leia mais

PROGRAMA DE PÓS-GRADUAÇÃO EM ENGENHARIA ELÉTRICA. Plano de Ensino

PROGRAMA DE PÓS-GRADUAÇÃO EM ENGENHARIA ELÉTRICA. Plano de Ensino DISCIPLINA: Tópicos Especiais em Sistemas Elétricos: Interação entre Descargas Atmosféricas e Sistemas Elétricos. CÓDIGO: MEE001 Validade: A partir do 1º semestre de 2009. Carga Horária: 45 horas-aula

Leia mais

Análise Probabilística das Solicitações Transitórias com Ênfase ao Religamento Automático de Linhas de Transmissão

Análise Probabilística das Solicitações Transitórias com Ênfase ao Religamento Automático de Linhas de Transmissão Análise Probabilística das Solicitações Transitórias com Ênfase ao Religamento Automático de Linhas de Transmissão Alécio B. Fernandes, Member, IEEE, e Antonio C. S. Lima, Member, IEEE Resumo -- Em estudos

Leia mais

A COMPARATIVE STUDY OF MODELING TRANSFORMER WINDINGS BY FINITE ELEMENT METHOD FOR ELECTROMECHANICAL STRESSES ANALYSIS

A COMPARATIVE STUDY OF MODELING TRANSFORMER WINDINGS BY FINITE ELEMENT METHOD FOR ELECTROMECHANICAL STRESSES ANALYSIS ESTUDO COMPARATIVO DE MODELAGENS DE ENROLAMENTOS DE UM TRANSFORMADOR UTILIZANDO O MÉTODO DOS ELEMENTOS FINITOS PARA ANÁLISES DE ESFORÇOS ELETROMECÂNICOS P. H. A. Barra¹, A. J. P. Rosentino Junior², A.

Leia mais

LT como Quadripolos. Os parâmetros ABCD são conhecidos como constantes genéricas do quadripolo equivalente de uma LT de parâmetros distribuídos:

LT como Quadripolos. Os parâmetros ABCD são conhecidos como constantes genéricas do quadripolo equivalente de uma LT de parâmetros distribuídos: LT como Quadripolos LT como Quadripolos LT como Quadripolos Os parâmetros ABCD são conhecidos como constantes genéricas do quadripolo equivalente de uma LT de parâmetros distribuídos: LT como Quadripolos

Leia mais

ANÁLISE TÉCNICA COMPARATIVA SOBRE O EMPREGO DE REATORES SATURADOS E LINEARES PARA A REGULAÇÃO DA TENSÃO EM SISTEMAS DE TRANSMISSÃO RADIAIS

ANÁLISE TÉCNICA COMPARATIVA SOBRE O EMPREGO DE REATORES SATURADOS E LINEARES PARA A REGULAÇÃO DA TENSÃO EM SISTEMAS DE TRANSMISSÃO RADIAIS ANÁLISE TÉCNICA COMPARATIVA SOBRE O EMPREGO DE REATORES SATURADOS E LINEARES PARA A REGULAÇÃO DA TENSÃO EM SISTEMAS DE TRANSMISSÃO RADIAIS A. B. Vasconcellos, Dr; F. P. Santilio, Acad; M. K. Kawaphara,

Leia mais

UMA PROPOSTA DE PROCEDIMENTO PARA A ANÁLISE DA QUALIDADE DA ENERGIA ELÉTRICA

UMA PROPOSTA DE PROCEDIMENTO PARA A ANÁLISE DA QUALIDADE DA ENERGIA ELÉTRICA UMA PROPOSTA DE PROCEDIMENTO PARA A ANÁLISE DA QUALIDADE DA ENERGIA ELÉTRICA Francis C. Pereira, Eng. José C. de Oliveira, PhD. Aloísio de Oliveira, Dr. Anderson L. A. Vilaça, Eng. Universidade Federal

Leia mais

GRUPO X GRUPO DE ESTUDO DE SOBRETENSÕES E COORDENAÇÃO DE ISOLAMENTO - GSC

GRUPO X GRUPO DE ESTUDO DE SOBRETENSÕES E COORDENAÇÃO DE ISOLAMENTO - GSC SNPTEE SEMINÁRIO NACIONAL DE PRODUÇÃO E TRANSMISSÃO DE ENERGIA ELÉTRICA GSC - 13 16 a 21 Outubro de 25 Curitiba - Paraná GRUPO X GRUPO DE ESTUDO DE SOBRETENSÕES E COORDENAÇÃO DE ISOLAMENTO - GSC ENERGIZAÇÃO

Leia mais

GRUPO X SOBRETENSÕES, COORDENAÇÃO DE ISOLAMENTO E INTERFERÊNCIAS - GSI

GRUPO X SOBRETENSÕES, COORDENAÇÃO DE ISOLAMENTO E INTERFERÊNCIAS - GSI GSI/ 6 17 a 22 de outubro de 1999 Foz do Iguaçu Paraná Brasil GRUPO X SOBRETENSÕES, COORDENAÇÃO DE ISOLAMENTO E INTERFERÊNCIAS - GSI USO DE MANOBRA SÍNCRONA PARA ELIMINAÇÃO DO RISCO DE DANIFICAÇÃO DE TRANSFORMADORES

Leia mais

Comentários sobre bobinas de Tesla

Comentários sobre bobinas de Tesla Comentários sobre bobinas de Tesla Por Antônio Carlos M. de Queiroz Este documento complementa um outro que escrevi sobre bobinas de Tesla, descrevendo alguns aspectos sobre o funcionamento de bobinas

Leia mais

XX SNPTEE SEMINÁRIO NACIONAL DE PRODUÇÃO E TRANSMISSÃO DE ENERGIA ELÉTRICA GRUPO DE ESTUDOS DE DESENVOLVIMENTO DE SISTEMAS ELÉTRICOS - GDS

XX SNPTEE SEMINÁRIO NACIONAL DE PRODUÇÃO E TRANSMISSÃO DE ENERGIA ELÉTRICA GRUPO DE ESTUDOS DE DESENVOLVIMENTO DE SISTEMAS ELÉTRICOS - GDS XX SNPTEE SEMINÁRIO NACIONAL DE PRODUÇÃO E TRANSMISSÃO DE ENERGIA ELÉTRICA 22 a 25 Novembro de 29 Recife - PE GRUPO - X GRUPO DE ESTUDOS DE DESENVOLVIMENTO DE SISTEMAS ELÉTRICOS - GDS CHAVES SECCIONADORAS

Leia mais

Impacto da transmissão da Copa do Mundo 2006 para a qualidade da energia elétrica nos sistemas de distribuição

Impacto da transmissão da Copa do Mundo 2006 para a qualidade da energia elétrica nos sistemas de distribuição 1 Impacto da transmissão da Copa do Mundo 6 para a qualidade da energia elétrica nos sistemas de distribuição José Rubens M. Jr, M. Sc. Alessandro G. Martins Jules Renato V. Carneiro Maria Jovita V. Siqueira

Leia mais

ESTUDO COMPARATIVO DE SOBRETENSÕES ATMOSFÉRICAS EM DIFERENTES MODELOS DE TORRES DE TRANSMISSÃO

ESTUDO COMPARATIVO DE SOBRETENSÕES ATMOSFÉRICAS EM DIFERENTES MODELOS DE TORRES DE TRANSMISSÃO ESTUDO COMPARATIVO DE SOBRETENSÕES ATMOSFÉRICAS EM DIFERENTES MODELOS DE TORRES DE TRANSMISSÃO ¹Raniere Varon Fernandes Mimoso (SENAI CIMATEC) raniere1994@hotmail.com; 2 Guilherme Saldanha Kroetz (SENAI

Leia mais

6LVWHPDGH6LPXODomRSDUD2EWHQomRGH'DGRV

6LVWHPDGH6LPXODomRSDUD2EWHQomRGH'DGRV 38 6LVWHPDGH6LPXODomRSDUD2EWHQomRGH'DGRV O sistema de identificação e localização de faltas utilizando RNAs necessita de um conjunto de registros de curto-circuito em diversas situações diferentes, para

Leia mais

ET720 Sistemas de Energia Elétrica I. Capítulo 4: Transformadores de potência. Exercícios

ET720 Sistemas de Energia Elétrica I. Capítulo 4: Transformadores de potência. Exercícios ET720 Sistemas de Energia Elétrica I Capítulo 4: Transformadores de potência Exercícios 4.1 Um transformador monofásico de dois enrolamentos apresenta os seguintes valores nominais: 20 kva, 480/120 V,

Leia mais

GRUPO X GRUPO DE ESTUDO DE SOBRETENSÕES E COORDENAÇÃO DE ISOLAMENTO - GSC

GRUPO X GRUPO DE ESTUDO DE SOBRETENSÕES E COORDENAÇÃO DE ISOLAMENTO - GSC SNPTEE SEMINÁRIO NACIONAL DE PRODUÇÃO E TRANSMISSÃO DE ENERGIA ELÉTRICA GSC - 14 16 a 21 Outubro de 2005 Curitiba - Paraná GRUPO X GRUPO DE ESTUDO DE SOBRETENSÕES E COORDENAÇÃO DE ISOLAMENTO - GSC CHAVEAMENTO

Leia mais

GRUPO XIII GRUPO DE ESTUDO DE INTERFERÊNCIAS, COMPATIBILIDADE ELETROMAGNÉTICA E QUALIDADE DE ENERGIA- GCQ

GRUPO XIII GRUPO DE ESTUDO DE INTERFERÊNCIAS, COMPATIBILIDADE ELETROMAGNÉTICA E QUALIDADE DE ENERGIA- GCQ SNPTEE SEMINÁRIO NACIONAL DE PRODUÇÃO E TRANSMISSÃO DE ENERGIA ELÉTRICA GCQ - 04 16 a 21 Outubro de 2005 Curitiba - Paraná GRUPO XIII GRUPO DE ESTUDO DE INTERFERÊNCIAS, COMPATIBILIDADE ELETROMAGNÉTICA

Leia mais

GRUPO X GRUPO DE ESTUDO DE SOBRETENSÕES E COORDENAÇÃO DE ISOLAMENTO (GSC)

GRUPO X GRUPO DE ESTUDO DE SOBRETENSÕES E COORDENAÇÃO DE ISOLAMENTO (GSC) GSC/017 21 a 26 de Outubro de 2001 Campinas - São Paulo - Brasil GRUPO X GRUPO DE ESTUDO DE SOBRETENSÕES E COORDENAÇÃO DE ISOLAMENTO (GSC) ESTUDOS DE TRANSITÓRIOS PARA A LICITAÇÃO DOS SISTEMAS DE TRANSMISSÃO

Leia mais

SVC Static VAr Compensator. Juliano Menezes Luis Gustavo Dias de Souza

SVC Static VAr Compensator. Juliano Menezes Luis Gustavo Dias de Souza SVC Static VAr Compensator Juliano Menezes Luis Gustavo Dias de Souza Introdução Excesso de reativo: Baixo FP; Aumento das correntes que percorrem os condutores, levando a maiores perdas; Punições, multas;

Leia mais

Sistemas Elétricos de Potência 1 Lista de Exercícios No. 6

Sistemas Elétricos de Potência 1 Lista de Exercícios No. 6 Sistemas Elétricos de Potência 1 Lista de Exercícios No. 6 1) Determine a corrente de curto-circuito trifásico em Ampères e em p.u. no ponto F da figura abaixo (lado de AT do trafo), desprezando-se a corrente

Leia mais

AVALIAÇÃO DOS EFEITOS DA CONEXÃO DE UMA UNIDADE GERADORA DISTRIBUÍDA A UM ALIMENTADOR DE 13,8 KV UTILIZANDO O ATP

AVALIAÇÃO DOS EFEITOS DA CONEXÃO DE UMA UNIDADE GERADORA DISTRIBUÍDA A UM ALIMENTADOR DE 13,8 KV UTILIZANDO O ATP AVALIAÇÃO DOS EFEITOS DA CONEXÃO DE UMA UNIDADE GERADORA DISTRIBUÍDA A UM ALIMENTADOR DE 3,8 KV UTILIZANDO O ATP Jaqueline O. Rezende, Larissa M. Peres, Geraldo C. Guimarães, Marcelo L. R. Chaves Universidade

Leia mais

Avaliação do Desempenho da Proteção de Distância Aplicada às Linhas de Transmissão com Pouco Mais de Meio Comprimento de Onda

Avaliação do Desempenho da Proteção de Distância Aplicada às Linhas de Transmissão com Pouco Mais de Meio Comprimento de Onda Avaliação do Desempenho da Proteção de Distância Aplicada às Linhas de Transmissão com Pouco Mais de Meio Comprimento de Onda Bernard F. Küsel, Mateus A. De Sordi e Kleber M. Silva Resumo Muitos tem sido

Leia mais

Fascículo. Capítulo X. Principais fenômenos, natureza e simetria da corrente de curto-circuito. Curto-circuito para a seletividade

Fascículo. Capítulo X. Principais fenômenos, natureza e simetria da corrente de curto-circuito. Curto-circuito para a seletividade 50 Curto-circuito para a seletividade Estudo de curto-circuito Capítulo X Principais fenômenos, natureza e simetria da corrente de curto-circuito Após o levantamento de dados, no escritório, elabora-se

Leia mais

Avaliação da Impedância Harmônica de uma Malha de Aterramento Submetida a Correntes Impulsivas

Avaliação da Impedância Harmônica de uma Malha de Aterramento Submetida a Correntes Impulsivas Avaliação da Impedância Harmônica de uma Malha de Aterramento Submetida a Correntes Impulsivas Felipe J. L de Araújo Edson G. da Costa Helder Alves Pereira Marconni F. B. R. Gonçalves João Marcelo Costa

Leia mais

TÍTULO: SISTEMA PARA ANÁLISE DE FENÔMENOS ELÉTRICOS RELACIONADOS COM A QUALIDADE DA ENERGIA FORNECIDA PELAS CONCESSIONÁRIAS

TÍTULO: SISTEMA PARA ANÁLISE DE FENÔMENOS ELÉTRICOS RELACIONADOS COM A QUALIDADE DA ENERGIA FORNECIDA PELAS CONCESSIONÁRIAS TÍTULO: SISTEMA PARA ANÁLISE DE FENÔMENOS ELÉTRICOS RELACIONADOS COM A QUALIDADE DA ENERGIA FORNECIDA PELAS CONCESSIONÁRIAS CATEGORIA: CONCLUÍDO ÁREA: CIÊNCIAS EXATAS E DA TERRA SUBÁREA: Engenharias INSTITUIÇÃO(ÕES):

Leia mais

Afundamentos de Tensão Provocados por Descargas Atmosféricas Indiretas

Afundamentos de Tensão Provocados por Descargas Atmosféricas Indiretas 1 Afundamentos de Tensão Provocados por Descargas Atmosféricas Indiretas L. C. Alves, UFMG, A. E. A. Araújo, UFMG, G. C. Miranda, UFMG Resumo Atualmente, transmitir e/ou distribuir energia elétrica com

Leia mais

GRUPO X SOBRETENSÕES, COORDENAÇÃO DE ISOLAMENTO E INTERFERÊNCIAS (GSI)

GRUPO X SOBRETENSÕES, COORDENAÇÃO DE ISOLAMENTO E INTERFERÊNCIAS (GSI) GSI/ 08 17 a 22 de outubro de 1999 Foz do Iguaçu Paraná Brasil GRUPO X SOBRETENSÕES, COORDENAÇÃO DE ISOLAMENTO E INTERFERÊNCIAS (GSI) AVALIAÇÃO DA TENSÃO DE RESTABELECIMENTO TRANSITÓRIA (TRT) PARA DISJUNTORES

Leia mais

Lista de exercícios de: Circuitos Elétricos de Corrente Alternada Prof.: Luís Fernando Pagotti

Lista de exercícios de: Circuitos Elétricos de Corrente Alternada Prof.: Luís Fernando Pagotti nome: Parte I Conceitos de Corrente Alternada e de Transformada Fasorial 1 a Questão: (a) Converta as ondas senoidais de tensão e corrente em seus respectivos fasores, indicando-os em um diagrama fasorial.

Leia mais

3 Avaliação da segurança dinâmica de sistemas de energia elétrica: Resultados

3 Avaliação da segurança dinâmica de sistemas de energia elétrica: Resultados 3 Avaliação da segurança dinâmica de sistemas de energia elétrica: Resultados 3.1 Introdução O presente capítulo apresenta os resultados obtidos da aplicação do método de avaliação da segurança dinâmica

Leia mais

XVIII Seminário Nacional de Distribuição de Energia Elétrica

XVIII Seminário Nacional de Distribuição de Energia Elétrica XVIII Seminário Nacional de Distribuição de Energia Elétrica SENDI 2008-06 a 10 de outubro Olinda - Pernambuco - Brasil Impacto da transmissão da Copa do Mundo 2006 para a qualidade da energia elétrica

Leia mais

XX SNPTEE SEMINÁRIO NACIONAL DE PRODUÇÃO E TRANSMISSÃO DE ENERGIA ELÉTRICA

XX SNPTEE SEMINÁRIO NACIONAL DE PRODUÇÃO E TRANSMISSÃO DE ENERGIA ELÉTRICA XX SNPTEE SEMINÁRIO NACIONAL DE PRODUÇÃO E TRANSMISSÃO DE ENERGIA ELÉTRICA Versão 1.0 XXX.YY 22 a 25 Novembro de 2009 Recife - PE GRUPO VIII GRUPO DE ESTUDO DE SUBESTAÇÕES E EQUIPAMENTOS DE ALTA TENSÃO

Leia mais

TRABALHO FINAL DE GRADUAÇÃO JUNHO/2014 UNIVERSIDADE FEDERAL DE ITAJUBÁ ENGENHARIA ELÉTRICA

TRABALHO FINAL DE GRADUAÇÃO JUNHO/2014 UNIVERSIDADE FEDERAL DE ITAJUBÁ ENGENHARIA ELÉTRICA TRABALHO FINAL DE GRADUAÇÃO JUNHO/2014 UNIVERSIDADE FEDERAL DE ITAJUBÁ ENGENHARIA ELÉTRICA ANÁLISE DO COMPORTAMENTO TRANSITÓRIO DE DISJUNTORES EM SUBESTAÇÕES ELÉTRICAS DE ALTA TENSÃO Huggo Rhodrigo Soares

Leia mais

B CE B4 MODERNIZAÇÃO E REPOTENCIAÇÃO DE FACTS E HVDC DA ESTAÇÃO INVERSORA DE IBIÚNA NECESSIDADE, ESPECIFICAÇÃO E PROJETO. José Roberto Medeiros

B CE B4 MODERNIZAÇÃO E REPOTENCIAÇÃO DE FACTS E HVDC DA ESTAÇÃO INVERSORA DE IBIÚNA NECESSIDADE, ESPECIFICAÇÃO E PROJETO. José Roberto Medeiros CE B4 MODERNIZAÇÃO E REPOTENCIAÇÃO DE FACTS E HVDC B 4 0 3 ELO DE ITAIPU - FILTROS DE 3 o /5 o HARMÔNICOS DA ESTAÇÃO INVERSORA DE IBIÚNA NECESSIDADE, ESPECIFICAÇÃO E PROJETO Ricardo Ricardo André Gonçalves

Leia mais

A INFLUÊNCIA DA ESCOLHA DO MODELO DE PARA-RAIOS NOS ESTUDOS DE MELHORIA DE DESEMPENHO DAS LINHAS DE TRANSMISSÃO FRENTE A DESCARGAS ATMOSFÉRICAS

A INFLUÊNCIA DA ESCOLHA DO MODELO DE PARA-RAIOS NOS ESTUDOS DE MELHORIA DE DESEMPENHO DAS LINHAS DE TRANSMISSÃO FRENTE A DESCARGAS ATMOSFÉRICAS Foz do Iguaçu, Brasil XVIII ERIAC DÉCIMO OITAVO ENCONTRO REGIONAL IBERO-AMERICANO DO CIGRE 19 a 23 de maio de 2019 CE-NN Comitê de Estudos C4 Desempenho de sistemas elétricos A INFLUÊNCIA DA ESCOLHA DO

Leia mais

Diagnóstico das condições operativas de disjuntores alimentadores de bancos de capacitores com a termografia infravermelha

Diagnóstico das condições operativas de disjuntores alimentadores de bancos de capacitores com a termografia infravermelha alimentadores de bancos de capacitores com a termografia infravermelha Alexsandro Teixeira Gomes PN/MT Gerência de Planejamento e Engenharia de Manutenção da Transmissão ICON Curso de Gerenciamento de

Leia mais

Análise Efeito Controle

Análise Efeito Controle 146 7 Análise do Efeito do Controle de Tensão com Compensadores Estáticos de Reativos (CER) em um Sistema-Teste de 39 Barras, em Regime Permanente e Dinâmico 7.1 Introdução Neste capítulo, para comprovar

Leia mais

TE 274 Tópicos Avançados em Eletrônica I. Cap. 7 Variação de tensão em regime permanente. Prof. Mateus Duarte Teixeira (por J.C.

TE 274 Tópicos Avançados em Eletrônica I. Cap. 7 Variação de tensão em regime permanente. Prof. Mateus Duarte Teixeira (por J.C. TE 274 Tópicos Avançados em Eletrônica I Cap. 7 Variação de tensão em regime permanente Prof. Mateus Duarte Teixeira (por J.C. Oliveira) 1. Definição Variações de tensão de longa duração são desvios que

Leia mais

4 Cálculo de Equivalentes Dinâmicos

4 Cálculo de Equivalentes Dinâmicos 4 Cálculo de Equivalentes Dinâmicos 4.1. Introdução Os sistemas de potência interligados vêm adquirindo maior tamanho e complexidade, aumentando a dependência de sistemas de controle tanto em operação

Leia mais

PROJETO DE DIPLOMAÇÃO

PROJETO DE DIPLOMAÇÃO UNIVERSIDADE FEDERAL DO RIO GRANDE DO SUL ESCOLA DE ENGENHARIA DEPARTAMENTO DE ENGENHARIA ELÉTRICA JORGE ANDRÉ MENEGHEL JITSUKAWA PROJETO DE DIPLOMAÇÃO COORDENAÇÃO DE ISOLAMENTO DE SUBESTAÇÕES ISOLADAS

Leia mais

XX SNPTEE SEMINÁRIO NACIONAL DE PRODUÇÃO E TRANSMISSÃO DE ENERGIA ELÉTRICA

XX SNPTEE SEMINÁRIO NACIONAL DE PRODUÇÃO E TRANSMISSÃO DE ENERGIA ELÉTRICA XX SNPTEE SEMINÁRIO NAIONAL DE PRODUÇÃO E TRANSMISSÃO DE ENERGIA ELÉTRIA 22 a 25 Novembro de 29 Recife - PE GRUPO -IV GRUPO DE ESTUDO GAT ANÁLISE DA INSERÇÃO SEM SUESSO DO REATOR 3 MVAR NO TERMINAL ABERTO

Leia mais

Investigação da Interação Simpática entre Transformadores Causada pela Corrente de Inrush

Investigação da Interação Simpática entre Transformadores Causada pela Corrente de Inrush Investigação da Interação Simpática entre Transformadores Causada pela Corrente de Inrush Herivelto de Souza Bronzeado Companhia Hidro Elétrica do São Francisco - CHESF Recife/PE, Brasil RESUMO Em sistemas

Leia mais